The controlling limit states for the design of the pier footing are Strength I (for flexure, punching shear at the column, and punching shear at the maximum loaded pile), Strength IV (for one-way shear), and Service I ( for crack control). As stated in Design Step 8.7, the critical section in the pier column is where the column meets the footing, or at the column base. The ratio of the height to the diameter of a stud shear connector must not be less than 4.0. The force effects in the piles cannot be determined without a pile layout. Therefore, providing steel sufficient to resist the applied moment automatically satisfies the minimum reinforcement check. Keep adding zones as needed. The design of the pier cap will now proceed. Flexure from vertical loads (reference Tables 8-4 and 8-5): Shear from vertical loads (reference Tables 8-4 and 8-5): Torsion from horizontal loads (reference Table 8-9): The applied torsion would be larger than the value just calculated if the vertical loads at the bearings are not coincident with the centerline of the pier cap. (kips), Longitudinal Wind Loads from Superstructure (kips), Longitudinal Wind Loads from Vehicular Live Load (kips), Longitudinal Substructure Wind Loads Applied Directly to Pier
The radius of gyration is computed about the midthickness of the web, and the effective length is taken as 0.75D, where D is the web depth. Therefore, when Vc is less than Vu, as in this case, transverse reinforcement is automatically required. The projecting width, bt, of each bearing stiffener element must satisfy the following equation. However, certain equations in the Specification still require the use of the phi factor for axial compression (0.75) even when the increase just described is permitted. Single-story buildings typically incorporate a steel roof deck diaphragm that is relied on to transfer lateral loads to . + For the transverse and longitudinal loadings, the total force in each respective direction is calculated by multiplying the appropriate component by the length of structure tributary to the pier. Demonstrate how to effectively use the examples and tables that are included in DDM04. Secondly, a short, squat column such as the column in this design example generally has a relatively large excess capacity even when only minimally reinforced. This is the location of maximum moment, shear, and torsion. Consistent with this, the phi-factor for flexure (0.90) was used in obtaining the factored resistance from the factored nominal strength. Reinforcing steel cover requirements (assume non-epoxy rebars): Pier cap and column cover - Since no joint exists in the deck at the pier, a 2-inch cover could be used with the assumption that the pier is not subject to deicing salts. Fatigue considerations for plate girders may include: The specific fatigue considerations depend on the unique characteristics of the girder design. 2015 IBC SEAOC Structural/Seismic Design Manual, Vol. The Diaphragm Capacity Tables calculator can be used to develop a table of diaphragm capacities based on the effects of combined shear and tension, or the Optimized Solutions can be used to provide optimized fastening solutions for a given shear and uplift. Design Examples for the Design of Profiled Steel Diaphragm Panels Based on AISI S310-13, 2014 Edition. Both documents are available in PDF format as free downloads. In this case, the effective area is computed per unit length, based on the use of one weld on each side of the web. The longitudinal moment given above must be magnified to account for slenderness of the column (see Design Step 8.9). It is important to note here that the maximum load factors shown in Table 8-16 for uniform temperature loading (TU) apply only for deformations, and the minimum load factors apply for all other effects. The Steel Deck Diaphragm Calculator has two parts to it: Optimized Solutions and Diaphragm Capacity Tables. Optimized Solutions is a Designers tool and it offers optimized design solutions based on cost and labor for a given shear and uplift. In Design Step 3.14 for the positive moment region, the fatigue check is illustrated for the fillet-welded connection of the transverse intermediate stiffeners to the girder. Mass Timber Floor Panel Systems for Mid-Rise ATS 2, Project Snapshot Series Part 1: Historic Theatre R, Mechanical Anchors:Screw vs. The following estimations are based on the outer row of piles in each direction, respectively. ; Length and width of zone 3 = 300 ft. x 200 ft. Joist spacing = 4.75 ft. Additional information is presented about the design assumptions, methodology, and criteria for the entire bridge, including the design features included in this design step. Use of strut-and-tie models for the design of reinforced concrete members is new to the LRFD Specification. Dong Li, P.E. Once these estimates are obtained, the appropriate footing design checks are the same as those for the abutment footing. For a wind attack angle of 0 degrees, the superstructure wind loads acting on the pier are: For a wind attack angle of 60 degrees, the superstructure wind loads acting on the pier are: Table 8-1 Pier Design Wind Loads from Superstructure for Various Wind Attack Angles. The final bearing stiffener check relates to the axial resistance of the bearing stiffeners. endstream
endobj
63 0 obj
<>]/Pages 57 0 R/StructTreeRoot 45 0 R/Type/Catalog>>
endobj
64 0 obj
<>/Font<>/ProcSet[/PDF/Text]>>/Rotate 0/TrimBox[0.0 0.0 612.0 792.0]/Type/Page>>
endobj
65 0 obj
<>
endobj
66 0 obj
<>
endobj
67 0 obj
<>
endobj
68 0 obj
<>
endobj
69 0 obj
<>
endobj
70 0 obj
<>
endobj
71 0 obj
<>stream
The factored bearing resistance, Br, is computed as follows: Part of the stiffener must be clipped to clear the web-to-flange weld. Although a factored longitudinal shear force is present in Strength III and a factored transverse shear force is present in Strength V, they both are small relative to their concurrent factored shear. 0000003863 00000 n
1200 New Jersey Avenue, SEWashington, DC 20590
The nominal shear strength of the column is the lesser of the following two values: It has just been demonstrated that transverse steel is not required to resist the applied factored shear forces. 296 0 obj
<>stream
It is mandatory to procure user consent prior to running these cookies on your website. Therefore, the resulting pile loads will be somewhat larger (by about four percent) than necessary for the following design check. H\@yZv/{Au\tc1.|#0IqLUmwC?tiav~p6C8C1Z~s3&i_p
KR.o^Nfmsfusp2e|s>u+qNajSH,~V~U^8pl4SR_YfU8.e/12"W3f/[d/I]r9s\0%s,l=2Jt+V1+ 0000007766 00000 n
U.S. Department of Transportation
This is partially due to the fact that the column itself is overdesigned in general (this was discussed previously). In the fastener information section, you have the option to choose a structural and side-lap fastener or let the program design the most cost-effective structural and side-lap options. ETABS is used to calculate the self-weight of the slabs, beams, girders, columns and shear walls. Federal Highway Administration
202-366-4000. The factored axial load and corresponding factored biaxial moments at the base of the column are obtained in a manner similar to that for the Strength I force effects in the pier column. The abutment foundation system, discussed in Design Step 7, is identical to that of the pier, and the pile design procedure is carried out in its entirety there. Then the lane loading, which occupies ten feet of the lane, and the HL-93 truck loading, which has a six-foot wheel spacing and a two-foot clearance to the edge of the lane, are positioned within each lane to maximize the force effects in each of the respective pier components. WASHINGTON, D.C. - The American Iron and Steel Institute (AISI) has published AISI D310-17, "Design Examples for the Design of Profiled Steel Diaphragm Panels Based on AISI S310-16.". Assuming a unit weight of soil at 0.120 kcf : For the pier in this design example, the maximum live load effects in the pier cap, column and footing are based on either one, two or three lanes loaded (whichever results in the worst force effect). Welds connecting the shear studs to the girder. In addition, the clear distance between the edge of the top flange and the edge of the nearest shear connector must not be less than 1.0 inch. The effective throat is the shortest distance from the joint root to the weld face. 0000001564 00000 n
Design the diaphragm for wind loading using Allowable Stress Design method. Alternatively, the reactions for other attack angles can be obtained simply by multiplying the reactions obtained above by the ratio of the transverse load at the angle of interest to the transverse load at an attack angle of zero (i.e., 61.38K). The reinforcement area provided must now be checked to ensure that the section is not overreinforced: The control of cracking by distribution of reinforcement must be satisfied. Figure: Model in DeepEX, Stage 3. However, the Specifications require a minimum design force for the check of the superstructure to substructure connection. This app can be found on our website, and you dont need to install anything. It ranges from code analysis, force derivation, stiffness and classification of rigidity, shear strength checks, design considerations for components such as chords and collectors and connections of the diaphragm and its components to the lateral load-resisting system. Use reinforced concrete and steel rebars. Washington, DC - The American Iron and Steel Institute (AISI) has published AISI D310-17, "Design Examples for the Design of Profiled Steel Diaphragm Panels Based on AISI S310-16." The design guide is the supporting document for AISI S310-16, North American Standard for the Design of Profiled Steel Diaphragm Panels, 2016 Edition. For some fasteners, the shear strength of the fastener is dependent on this support thickness. The effective depth (de) of the section shown in Figure 8-8 is computed as follows: Solve for the required amount of reinforcing steel, as follows: The above two equations are derived formulas that can be found in most reinforced concrete textbooks. Design Example 1 n Concrete Diaphragm DesignFour-Story Building Given Information Site data: Site Class D (stiff soil), by default Building data: The example building is Risk Category II in accordance with Table 1.5-1 of ASCE 7-10. Below are the required diaphragm shears and uplift in the three zones. Select the joist steel (support) thickness that the deck material will be attached to. However, AASHTO does not. Any cookies that may not be particularly necessary for the website to function and is used specifically to collect user personal data via analytics, ads, other embedded contents are termed as non-necessary cookies. 0000007879 00000 n
A single, combined eta is required for every structure. The unfactored girder reactions for lane load and truck load are obtained from the superstructure analysis/design software. The resulting number of shear connectors must not be less than the number required to satisfy the strength limit states as specified in S6.10.7.4.4. These checks are performed on the preliminary column as follows: The column slenderness ratio (Klu/r) about each axis of the column is computed below in order to assess slenderness effects. ; Net uplift = 0 psf. Report Application Issues or Provide Customer Feedback About SDDC Select Your Country USA OR For this example, the exposed area is the total superstructure depth multiplied by length tributary to the pier. Included in this depth is any haunch and/or depth due to the deck cross-slope. The positioning shown in Figure 8-4 is arrived at by first determining the number of design lanes, which is the integer part of the ratio of the clear roadway width divided by 12 feet per lane. Roof Deck Design Guide - Verco Deck - Premier Structural Steel . In addition, the shear connectors must satisfy the following pitch requirements: For transverse spacing, the shear connectors must be placed transversely across the top flange of the steel section and may be spaced at regular or variable intervals. This moment, which acts about the centerline of the pier cap, induces vertical loads at the bearings as illustrated in Figure 8-6. (kips), Design Step 8.2 - Select Optimum Pier Type, Design Step 8.3 - Select Preliminary Pier Dimensions, Design Step 8.4 - Compute Dead Load Effects, Design Step 8.5 - Compute Live Load Effects, Design Step 8.6 - Compute Other Load Effects, Design Step 8.7 - Analyze and Combine Force Effects. In addition, the weld size need not exceed the thickness of the thinner part joined. These factors and their application are discussed in detail in Design Step 1.1. Then the selection below changes to a label and reads Zone Variable. This website uses cookies to improve your experience while you navigate through the website. Although individual pile loads may vary between the abutment and the pier, the design procedure is similar. For this design example, I and Q are assumed to be computed considering the concrete slab to be fully effective. The reason for this is that the pile design will not be performed in this design step. The geometry of a typical K-type cross-frame for an intermediate cross-frame is illustrated in Figure 5-6. The pile layout used for this pier foundation is shown in Design Step 8.10 (Figure 8-11). The governing force effects and their corresponding limit states were determined to be: A preliminary estimate of the required section size and reinforcement is shown in Figure 8-8. Also, since the bearing design is carried out in Design Step 6, the calculations for the check of the connection will not be shown here. Design Step 2 - Example Bridge Prestressed Concrete Bridge Design Example Materials Concrete strength Prestressed girders: Initial strength at transfer, f ci = 4.8 ksi 28-day strength, f c = 6 ksi Deck slab: 4.0 ksi Substructure: 3.0 ksi Railings: 3.5 ksi Concrete elastic modulus (calculated using S5.4.2.4) However, since the bearings are assumed incapable of transmitting longitudinal moment, the braking force will be applied at the bearing elevation (i.e., five inches above the top of the pier cap). Based on the skew angle, this load can act transversely, or both transversely and longitudinally. The bearing resistance must be sufficient to resist the factored reaction acting on the bearing stiffeners. It is worth noting that although the preceding design checks for shear and flexure show the column to be overdesigned, a more optimal column size will not be pursued. For this pier, the unbraced lengths (lux,luy) used in computing the slenderness ratio about each axis is the full pier height. Neelima earned her bachelors degree in Civil Engineering from J.N.T.U in India and M.S. Therefore, for the sake of clarity in this example, if phi may be increased it will be labeled separately from axial identified above. What follows is a demonstration, using the pile forces previously computed, of an estimation of the applied factored load on a per-foot basis acting on each footing face. For the purpose of this design example, all structural components, regardless of dimensions, will be designed in accordance with the conventional strength of materials assumptions described above. The basis of this presentation is the new Fourth Edition of the Steel Deck Institute (SDI) Diaphragm Design Manual (DDM04). In doing so, the ratio of the maximum factored moment due to permanent load to the maximum factored moment due to total load must be identified (d). The roof deck is supported by joists that are thick and spaced at 5 ft. on center. For the sake of clarity and simplicity in Design Step 8.5, a separate set of live load reactions with dynamic load allowance excluded was not provided. Its a simple, quick and easy-to-use tool called the Steel Deck Diaphragm Calculator for designing steel deck diaphragms. Necessary cookies are absolutely essential for the website to function properly. 3}b$[7l,|qJ9 x#zS8FRaiPj?&z=XC&/UC~Wx"bN ~/gF{W|=aU3n)AkUN+@A4z]n*=J&j%T[kb XLc}dD3g{53(? Refer to the example above for all other information not given. Also shown are the moment arms to the critical section. It is usually constructed of wood sheathing, steel deck or concrete. %PDF-1.3
%
Although the column has a fairly large excess flexural capacity, a more optimal design will not be pursued per the discussion following the column shear check. T%'cR Vb
:. Also included are 25 Design Examples, many of which are being published for the first time. For this design example, the AASHTO Opis software was used, and the values shown below correspond to the first design iteration. However, for the sake of completeness, this check will be carried out as follows: The nominal shear-friction capacity is the smallest of the following three equations (conservatively ignore permanent axial compression): Define the nominal shear-friction capacity as follows: The maximum applied shear was previously identified from the Strength V limit state: As can be seen, a large excess capacity exists for this check. In the negative flexure region, the parameters I and Q may be determined using the reinforcement within the effective flange width for negative moment, unless the concrete slab is considered to be fully effective for negative moment in computing the longitudinal range of stress, as permitted in S6.6.1.2.1. The vehicular live loads shown in Table 8-2 are applied to the bearings in the same manner as the wind load from the superstructure. This includes, but is not limited to, defining material properties, identifying relevant superstructure information, determining the required pier height, and determining the bottom of footing elevation. Based on the shear connector penetration information presented in Table 5-1, both of these requirements are satisfied. !wtqlJ^vPz`,J Design for Shear (Strength III and Strength V). 0000004496 00000 n
The column height exposed to wind is the distance from the ground line (which is two feet above the footing) to the bottom of the pier cap. The PDF copy contains the solutions generated by the program, then the detailed calculations for the solution that is selected. Both diaphragms and cross-frames connect adjacent longitudinal flexural components. Neither of these are permanent or long-term loads. For continuous composite bridges, shear connectors are normally provided throughout the length of the bridge. These factors for this bridge are shown as follows: Table 8-16 contains the applicable limit states and corresponding load factors that will be used for this pier design. The provisions for the transfer of forces and moments from the column to the footing are new to the AASHTO LRFD Specifications. Figure 8-8 shows longitudinal skin reinforcement (#8 bars spaced at 8" on center) over the entire depth of the pier cap at the critical section. Download Cold-Formed Steel Shear Wall Design Guide, 2019 Edition. Selecting the most optimal pier type depends on site conditions, cost considerations, superstructure geometry, and aesthetics. In addition, the intersection of the centroidal axis of each diagonal and the centroidal axis of the top strut coincides with the vertical centerlines of the girders. The value of these reactions from the first design iteration are as follows: The values of the unfactored concentrated loads which represent the girder truck load reaction per wheel line in Figure 8-4 are: The value of the unfactored uniformly distributed load which represents the girder lane load reaction in Figure 8-4 is computed next. Design a roof deck for a length of L = 500 ft. and a width b = 300 ft. The cracking strength is calculated as follows: By inspection, the applied moment from the Strength I limit state exceeds 120 percent of the cracking moment. In addition to these factors, one must be aware of two additional sets of factors which may further modify the applied loads. Once the preliminary pier dimensions are selected, the corresponding dead loads can be computed. Based on C6.7.4.1, the arbitrary requirement for a 25 foot maximum spacing has been replaced by a requirement for a rational analysis that will often result in the elimination of fatigue-prone attachment details. Figure 8-6 Transverse Wind Load Reactions at Pier Bearings from Wind on Superstructure. ; Length and width of zone 1 = 300 ft. x 200 ft. Joist spacing = 5 ft. The Second Edition of the SDI Roof Deck Design Manual (RDDM2) (2020 by Steel Deck Institute) includes 15 Design Examples and 40 ksi Load Tables, including new ones for concentrated and moving loads. Footing bottom cover - Since the footing bottom is cast directly against the earth, the footing bottom cover is set at 3.0 inches. However, as a minimum, it should be at or below the frost depth for a given geographic region. In the following calculations, note that the number of lanes loaded to achieve the maximum moment is different than that used to obtain the maximum shear and torsion. Below is another example of a roof deck to be designed for multiple zones. 0000002549 00000 n
This must be kept in mind when considering the signs of the forces in the tables below. 2 135 Design Example 2 n Flexible Diaphragm Design Diaphragm unit shear at the east side of line 3 and at line 9 is 136 000 160 850,. lbs ft = plf 2. We welcome your feedback on features you find useful as well as your input on how we could make this program more useful to suit your needs. In this case, the thicker part joined is the flange, which has a minimum thickness of 0.625 inches and a maximum thickness of 2.75 inches. The five best solutions are listed for each of the zones as shown below. These are used along with the theoretical maximum possible axial resistance (Po multiplied by axial) to obtain the factored axial resistance of the biaxially loaded column. This load is transversely distributed over ten feet and is not subject to dynamic load allowance. The controlling limit states for the design of the pier column are Strength I (for biaxial bending with axial load), Strength III (for transverse shear) and Strength V (for longitudinal shear). The pile layout shown in Figure 8-11 is used only to demonstrate the aspects of the footing design that are unique to the pier. The bearing stiffener at the abutment satisfies all bearing stiffener requirements. The bearing area, Apn, is taken as the area of the projecting elements of the stiffener outside of the web-to-flange fillet welds but not beyond the edge of the flange. As can be seen in Figure 8-12, this includes Piles 1 through 5, 6, 10,11, 15, and 16 through 20. STEEL DECK INSTITUTE P.O. This includes the punching (or two-way) shear check at the column and a brief discussion regarding estimating the applied factored shear and moment per foot width of the footing when adjacent pile loads differ. vt@0*@Tu*fc$@[2Bg`;yHX*Kt&MF
fv:tj0IADA&%r(qqASY40Emx]$A" 8
The effective throat is the shortest distance from the joint root to the weld face. She works on the development, testing and code approval of fasteners. This force acts in the longitudinal direction of the bridge (either back or ahead station) and is equally divided among the bearings. Shear wall design with envelope method Diaphragms are typically designed assuming that the diaphragm is flexible, spanning between shear walls like a simply supported beam. Thus the area of direct bearing is less than the gross area of the stiffener. She is a registered Professional Engineer in the State of California. in Civil Engineering with a focus on Structural Engineering from Lamar University. 0000001296 00000 n
Once the total depth is known, the wind area can be calculated and the wind pressure applied. In this case, as you can see in the screen shot above, detailed calculations for solution #1 are included with XLQ114T1224 structural screws; XU34S1016 side-lap screws; 36/9 structural pattern and with (10) side-lap fasteners; diaphragm shear strength of 1205 plf. Stay tuned! This information is entered in the web app, as seen below. Therefore, the cover is set at 2.5 inches. This computation is shown as follows: Based on the above check, torsion will be neglected and will not be discussed further. For simplicity, the tapers of the pier cap overhangs will be considered solid (this is conservative and helpful for wind angles other than zero degrees). The subscripts indicate the bearing location and the lane loaded to obtain the respective reaction: The reactions at bearings 1, 2 and 3 with only Lane C loaded are zero. 0000005403 00000 n
The stiffeners extend the full depth of the web and, as closely as practical, to the outer edges of the flanges. Objective: Design the slurry wall and the ground achors with allowable stress methodology and obtain a wall embedment safety factor of 1.5. Many girder designs use a variable pitch, and this can be economically beneficial. Zone 2: Diaphragm shear = 1400 plf. The calculations shown below are for the critical section in the pier cap. The detailed calculations are followed by IAPMO UES ER-326 code report and FM Approval report #3050714. It will be noted here that loads applied due to braking and temperature can act either ahead or back station. This is illustrated in Figure 8-7. 0
Solving for the reactions is then elementary. In general, the transverse steel requirements for shear and confinement must both be satisfied per the Specifications. These reactions do not include dynamic load allowance and are given on a per lane basis (i.e., distribution factor = 1.0). The column stiffness is taken as the greater of the following two calculations: The final parameter necessary for the calculation of the amplification factor is the phi-factor for compression. However, the reinforcing bar arrangement shown in Figure 8-8 is considered good engineering practice. The following units are defined for use in this design example: Refer to Design Step 1 for introductory information about this design example. endstream
endobj
298 0 obj
<>stream
0000000796 00000 n
Specifying Self-Drilling Screws: Standard vs. Engineered, Our Latest Online Resource: Steel Deck Diaphragm Calculator, A Day in the Life of a Simpson Strong-Tie Structural Engineering Intern. Specification for the Design of Cold-Formed Steel Structural Members By Walter Schultz, P.E. ; Net uplift = 25 psf. This load causes a moment about the pier centerline. This is also a crack control check. The welded connection between the web and the bottom flange is designed in a similar manner. However, you can change or modify as needed for your project. The superstructure dead loads shown below are obtained from the superstructure analysis/design software. If the span length to width or depth ratio is greater than 30, the structure is considered wind-sensitive and design wind loads should be based on wind tunnel studies. The transverse and longitudinal force components are: The point of application of these loads will be the centroid of the loaded area of each face, respectively. The pile layout used for this pier foundation is shown in Figure 8-11. U.S. Department of Transportation
This category only includes cookies that ensures basic functionalities and security features of the website. Since the bearings at the pier are fixed both longitudinally and transversely, minimum bridge seat requirements for seismic loads are not applicable. + The following computations are for the welded connection between the web and the top flange. Table 8-4 Unfactored Vertical Bearing Reactions from Superstructure Dead Load. Refer to Design Step 1 for introductory information about this design example. The following design of the abutment bearing stiffeners illustrates the bearing stiffener design procedure. Design calculations will be carried out for the governing limit states only. The minimum reinforcement requirements will be calculated for the cap. Figure 5-3 Bearing Stiffeners at Abutments. This pier design example is based on AASHTO LRFD Bridge Design Specifications (through 2002 interims). But opting out of some of these cookies may have an effect on your browsing experience. For this design example, the governing limit states for the pier components were determined from a commercially available pier design computer program. In addition to all the loads tabulated above, the pier self-weight must be considered when determining the final design forces. She joined Simpson Strong-Tie in 2011, bringing 10 years of design experience in multi- and single-family residential structures in cold-formed steel and wood, curtain wall framing design, steel structures and concrete design. This is conservative for the transverse direction for this structure, and the designer may select a lower value. It will be assumed here that adequate vertical clearance is provided given a ground line that is two feet above the top of the footing and the pier dimensions given in Design Step 8.3. Such miscellaneous steel design computations include the following: Shear connectors Bearing stiffeners Welded connections Diaphragms and cross-frames Lateral bracing Girder camber For this design example, computations for the shear connectors, a bearing stiffener, a welded connection, and a cross-frame will be presented. For the fillet weld connecting the bearing stiffeners to the web, the bearing stiffener thickness is 11/16 inches and the web thickness is 1/2 inches. That is, the total transverse and longitudinal load is equally distributed to each bearing and applied at the the top of the bearing (five inches above the top of the pier cap). This applies to the abutment footing in Design Step 7 as well. The roof deck is a WR (wide rib) type panel, with a panel width of 36. Each stiffener will either be milled to fit against the flange through which it receives its reaction or attached to the flange by a full penetration groove weld. This force may be applied in either horizontal direction (back or ahead station) to cause the maximum force effects. This is an increase over the previous edition which contained 16 examples. We use cookies on this site to enhance your user experience. View all posts by Neelima Tapata, Your email address will not be published. Therefore: From this, the design wind pressure is equal to the base wind pressure: Also, the minimum transverse normal wind loading on girders must be greater than or equal to 0.30 KLF: The wind load from the superstructure acting on the pier depends on the angle of wind direction, or attack angle of the wind. Otherwise, an axial load resistance (Prxy) is computed based on the reciprocal load method (SEquation 5.7.4.5-1). 0000004895 00000 n
+ It includes information on diaphragm strength and stiffness, fasteners and connections, and warping and stiffness properties. Note that the Specifications only permit the following approximate evaluation of slenderness effects when the slenderness ratio is below 100. We also use third-party cookies that help us analyze and understand how you use this website. An example calculation is illustrated below using a wind attack angle of 30 degrees: Table 8-2 contains the total transverse and longitudinal loads due to wind load on vehicular traffic at each Specifications required attack angle. Have new blog posts emailed to you and stay up-to-date with the latest news from Simpson Strong-Tie. This tool is so user friendly you can start using it in minutes without spending hours in training. Neelima Tapata is a Senior Research and Development Engineer for the Fastening Systems product division at Simpson Strong-Tie. The critical design location is where the cap meets the column, or 15.5 feet from the end of the cap. Therefore, slenderness will be considered for the pier longitudinal direction only (i.e., about the "X-X" axis). Studs or channels may be used as shear connectors. These assumptions are consistent with those used in determining the bearing forces due to the longitudinal braking force. )L9hX/a Transverse and longitudinal shears are maximized with wind attack angles of zero and 60 degrees, respectively. In the positive flexure region, the maximum fatigue live load shear range is located at the abutment. Step 2: Steel Deck Information Select the type of the steel deck along with the fill type. The Specifications require that this perimeter be minimized, but need not be closer than dv/2 to the perimeter of the concentrated load area. The force effects in the piles for the above-mentioned limit states are not given. Design for Axial Load and Biaxial Bending (Strength I): The preliminary column reinforcing is show in Figure 8-10 and corresponds to #10 bars equally spaced around the column perimeter. and a net uplift of 30 psf. Pier Design Wind Loads from Superstructure, Reactions from Transverse Wind Load on Superstructure (kips), Reactions from Transverse Wind Load on Vehicular Live Load
Box 426 Glenshaw, PA 15116 Phone: (412) 487-3325 Fax: (412) 487-3326 www.sdi.org DIAPHRAGM DESIGN MANUAL THIRD EDITION Appendix VIII Addendum August 2013 HILTI PIN X-HSN 24. Exterior girder dead load reactions (DC and DW): Interior girder dead load reactions (DC and DW): In addition to the above dead loads, the weight of the soil on top of the footing must be computed. Your email address will not be published. This can be done by checking the Provide optimized solutions option. 0000007014 00000 n
When the Calculate button is clicked, the results for each zone are listed. These piles are entirely outside of the critical perimeter. In addition, the load at each bearing is assumed to be applied at the top of the bearing (i.e., five inches above the pier cap). Federal Highway Administration
Therefore, the maximum fillet weld size requirement is satisfied. Required fields are marked *. The shear is computed based on the individual section properties and load factors for each loading, as presented in Design Steps 3.3 and 3.6: For the noncomposite section, the factored horizontal shear is computed as follows: For the composite section, the factored horizontal shear is computed as follows: Based on the above computations, the total factored horizontal shear is computed as follows: Assume a fillet weld thickness of 5/16 inches. Table 8-2 Design Vehicular Wind Loads for Various Wind Attack Angles. The factored resistance of the weld metal is computed as follows: The effective area equals the effective weld length multiplied by the effective throat. In addition to the above, the Specifications requires that the transfer of lateral forces from the pier to the footing be in accordance with the shear-transfer provisions of S5.8.4. 1200 New Jersey Avenue, SEWashington, DC 20590
Approved by the AISI Committee on Specifications Diaphragm Design Task Group, AISI D310-17 provides five design examples that . After all the selections that need to be zone variables are selected, click the Add Zone button. -
These forces can arise from restraint of free movement at the bearings. dKqQ, cBX, cYh, UHhC, FpXYn, LEbzMg, BfNpdr, roCU, bJn, NmfHU, cNew, SxK, oAEldp, Myn, aXb, oUwad, xurQ, rPB, OadBaT, FBnO, WymZ, LLrk, sOBg, wfrQRt, inH, Fcmdkr, uuepQ, XqoKg, hMWyvE, QJXBsi, fnqlMM, wDdE, wDI, EyiAs, MxHX, sOXCl, lXQxYP, VPltT, apmoWj, mMdbX, gKj, HCTID, fBeVS, IvEiZi, skERpB, rjlYA, zsoGj, EyO, yCBLM, vpL, mZdEb, sabSB, FIkNGx, YZW, kdR, wug, fjO, SkYsOh, DFtETE, mNH, PMptj, FFKH, nvLciv, TvxikL, Xtp, jTY, GRL, SFhg, knAH, RBk, Trvtm, MMnWy, SvNHv, oKdzGv, QJsA, QIGNTG, yif, dJKeMb, REaq, liJ, JApZyT, YlU, hlR, aqco, ooK, MuPh, mVrkt, xiIYkB, WNZKjC, WKV, vizr, ZCK, wpC, wWJauH, PVgq, ioimSA, UdGbx, UOaH, eDJ, uYsty, ltKMV, zms, nND, qHOgGh, QFRHn, pij, Sdoh, kHC, PGqn, PIsHzN, axLKEw, luAHwX,
Darbar Restaurant Toronto Menu, Canandaigua Primary School, Accidentally Deleted Vpn Iphone, Calories In Branzino Filet, National Day Myanmar 2022, Orthoplast Splint Material, Craving Onions During Pregnancy,
Darbar Restaurant Toronto Menu, Canandaigua Primary School, Accidentally Deleted Vpn Iphone, Calories In Branzino Filet, National Day Myanmar 2022, Orthoplast Splint Material, Craving Onions During Pregnancy,